Process History/Live Data

This includes any data stores that maintain historical or real-time events and telemetry recorded from various sensors or devices

ID: DC0107
Domains: ICS
Version: 2.1
Created: 11 May 2022
Last Modified: 13 October 2026

Log Sources

Name Channel
Databases None
Operational Databases None
operationaldb:ProcessHistory no new process value recorded for device_ip within 1.5x expected poll interval immediately following a flood alert
operationaldb:ProcessHistory process value crosses known alarm threshold but no corresponding alarm event recorded within expected latency window
operationaldb:ProcessHistory multiple safety-critical outputs toggle within rapid toggle window, pattern consistent with scripted issuance
operationaldb:ProcessHistory I/O point value oscillates or changes state at frequency exceeding max normal state change rate, inconsistent with physical process response time
operationaldb:ProcessHistory reported values show statistically improbable stability during a period when physical process is known to be actively changing
operationaldb:ProcessHistory tag value deviates from rolling baseline mean by more than parameter drift threshold percent within time window following a flagged write
operationaldb:ProcessHistory process value expected to change following a command does not change within command confirmation window
operationaldb:ProcessHistory no unsolicited report received from device_ip within 1.5x expected reporting interval, while direct polling confirms device is reachable
processsensor:RedundantComparison Independent process measurement comparison: controller I/O image value diverges from independent sensor/measurement beyond configured integrity tolerance

Detection Strategy