Detection of Device Restart/Shutdown

Technique Detected:  Device Restart/Shutdown | T0816

ID: DET0801
Domains: ICS
Analytics: AN1933, AN2157, AN2187, AN2260
Version: 1.0
Created: 21 October 2025
Last Modified: 13 October 2026

Analytics

AN1933

Real-time monitoring identifies an Industrial Control System (ICS) protocol restart/reset command directed at a field device from a source not in the approved engineering workstation list, particularly where multiple devices receive restart commands within a short window. Documented precedent: Industroyer exploited CVE-2015-5374 via a crafted 18-byte User Datagram Protocol (UDP) packet to port 50000 on Siemens SIPROTEC relays. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Log Sources
Data Component Name Channel
Device Alarm (DC0108) operationaldb:AlarmEvent more than one device generates restart/offline alarm within bulk restart time window without open maintenance ticket
Network Traffic Content (DC0085) NSM:Content restart/reset service from source not in engineering workstation list outside change control window
Network Traffic Flow (DC0078) NSM:Content non-standard or malformed packet to device-specific diagnostic port immediately preceding a device-offline alarm
Mutable Elements
Field Description
BulkRestartTimeWindow Time window within which multiple device restarts are considered a coordinated event.
ChangeControlWindow Scheduled maintenance periods during which restarts are authorized.
EngineeringWorkstationList IP allowlist of workstations authorized to issue device restart commands.

AN2157

Real-time monitoring identifies an Industrial Control System (ICS) Linux engineering tool issuing device restart commands outside a scheduled maintenance window, from a User Identifier (UID) not in the approved engineer list. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Log Sources
Data Component Name Channel
Process Creation (DC0032) auditd:SYSCALL Linux Audit SYSCALL/EXECVE/SOCKADDR records (configured audit rule): syscall=execve; device restart/shutdown command invoked outside the approved change-control window by an unauthorized UID
Mutable Elements
Field Description
BulkRestartTimeWindow Time window within which multiple device restarts are considered a coordinated event.
ChangeControlWindow Scheduled maintenance periods during which restarts are authorized.
EngineeringWorkstationList IP allowlist of workstations authorized to issue device restart commands.

AN2187

Real-time monitoring identifies Simple Network Management Protocol (SNMP) SET commands to power Management Information Base (MIB) restart Object Identifiers (OIDs) or Command Line Interface (CLI) reload commands from a source not in the approved Network Management System (NMS) Classless Inter-Domain Routing (CIDR). OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Log Sources
Data Component Name Channel
Application Log Content (DC0038) networkdevice:snmp Simple Network Management Protocol (SNMP) SET to power Management Information Base (MIB) restart Object Identifier (OID) or Command Line Interface (CLI) reload command from source not in approved Network Management System (NMS) Classless Inter-Domain Routing (CIDR) subnet
Mutable Elements
Field Description
BulkRestartTimeWindow Time window within which multiple device restarts are considered a coordinated event.
ChangeControlWindow Scheduled maintenance periods during which restarts are authorized.
EngineeringWorkstationList IP allowlist of workstations authorized to issue device restart commands.

AN2260

Real-time monitoring identifies Industrial Control System (ICS) vendor engineering software initiating a device restart command from a Windows host outside a scheduled maintenance window. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Log Sources
Data Component Name Channel
Application Log Content (DC0038) engineeringworkstation:ApplicationLog device restart command initiated outside change control window by account not in approved engineer list
Mutable Elements
Field Description
BulkRestartTimeWindow Time window within which multiple device restarts are considered a coordinated event.
ChangeControlWindow Scheduled maintenance periods during which restarts are authorized.
EngineeringWorkstationList IP allowlist of workstations authorized to issue device restart commands.