Block Communications: Serial COM

ID Name
T1695.001 Serial COM
T1695.002 Ethernet
T1695.003 Wi-Fi

Adversaries may block access to serial COM to prevent instructions or configurations from reaching target devices. Serial Communication ports (COM) allow communication with control system devices. Devices can receive command and configuration messages over such serial COM. Devices also use serial COM to send command and reporting messages. Blocking device serial COM may also block command messages and block reporting messages.

A serial to Ethernet converter is often connected to a serial COM to facilitate communication between serial and Ethernet devices. One approach to blocking a serial COM would be to create and hold open a TCP session with the Ethernet side of the converter. A serial to Ethernet converter may have a few ports open to facilitate multiple communications. For example, if there are three serial COM available -- 1, 2 and 3 --, the converter might be listening on the corresponding ports 20001, 20002, and 20003. If a TCP/IP connection is opened with one of these ports and held open, then the port will be unavailable for use by another party. One way the adversary could achieve this would be to initiate a TCP session with the serial to Ethernet converter at 10.0.0.1 via Telnet on serial port 1 with the following command: telnet 10.0.0.1 20001.

ID: T1695.001
Sub-technique of:  T1695
ⓘ
Platforms: Embedded, Linux, Network Devices, Windows
Version: 1.0
Created: 20 April 2026
Last Modified: 13 October 2026

Procedure Examples

ID Name Description
C0028 2015 Ukraine Electric Power Attack

During the 2015 Ukraine Electric Power Attack, Sandworm Team overwrote the serial-to-ethernet converter firmware, rendering the devices not operational. This meant that communication to the downstream serial devices was either not possible or more difficult. [1]

S0604 Industroyer

In Industroyer the first COM port from the configuration file is used for the actual communication and the two other COM ports are just opened to prevent other processes accessing them. Thus, the IEC 101 payload component is able to take over and maintain control of the RTU device. [2]

Targeted Assets

ID Asset
A0007 Control Server
A0009 Data Gateway
A0017 Distributed Control System (DCS) Controller
A0013 Field I/O
A0002 Human-Machine Interface (HMI)
A0005 Intelligent Electronic Device (IED)
A0012 Jump Host
A0018 Programmable Automation Controller (PAC)
A0003 Programmable Logic Controller (PLC)
A0004 Remote Terminal Unit (RTU)
A0010 Safety Controller
A0011 Virtual Private Network (VPN) Server
A0001 Workstation

Mitigations

ID Mitigation Description
M0807 Network Allowlists

Implement network allowlists to minimize serial comm port access to only authorized hosts, such as comm servers and RTUs.

M0930 Network Segmentation

Restrict unauthorized devices from accessing serial comm ports.

M0810 Out-of-Band Communications Channel

Ensure devices have an alternative method for communicating in the event that a valid COM port is unavailable.

Detection Strategy

ID Name Analytic ID Analytic Description
DET0797 Detection of Block Serial COM AN1929

Real-time monitoring identifies a loss of communication with serially-connected field devices correlated with a configuration change event on the serial-to-Ethernet gateway. Documented in the 2015 Ukraine attack, where Sandworm used malicious firmware to render serial-to-Ethernet converters inoperable. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

AN2119

Real-time monitoring identifies writes to serial device configuration files or stty commands changing serial port parameters on Industrial Control System (ICS) Linux gateway hosts from a User Identifier (UID) not associated with authorized serial port management. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

AN2200

Real-time monitoring identifies configuration changes to serial server or terminal server devices that alter serial port parameters for ports connected to field devices. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

AN2280

Real-time monitoring identifies Windows serial port configuration changes on Industrial Control System (ICS) gateway hosts that would disrupt communication with serial field devices. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.