Point & Tag Identification

Adversaries may collect point and tag values to gain a more comprehensive understanding of the process environment. Points may be values such as inputs, memory locations, outputs or other process specific variables. [1] Tags are the identifiers given to points for operator convenience.

Collecting such tags provides valuable context to environmental points and enables an adversary to map inputs, outputs, and other values to their control processes. Understanding the points being collected may inform an adversary on which processes and values to keep track of over the course of an operation.

ID: T0861
Sub-techniques:  No sub-techniques
ⓘ
Tactic: Collection
ⓘ
Platforms: Embedded, Linux, Network Devices, Windows
Contributors: Jos Wetzels - Midnight Blue
Version: 1.1
Created: 21 May 2020
Last Modified: 13 October 2026

Procedure Examples

ID Name Description
S0093 Backdoor.Oldrea

The Backdoor.Oldrea payload has the capability of enumerating OPC tags, in addition to more generic OPC server information. The server data and tag names can provide information about the names and function of control devices. [2] [3]

S1045 INCONTROLLER

INCONTROLLER can remotely read the OCP UA structure from devices.[4]

Targeted Assets

ID Asset
A0007 Control Server
A0009 Data Gateway
A0006 Data Historian
A0017 Distributed Control System (DCS) Controller
A0002 Human-Machine Interface (HMI)
A0005 Intelligent Electronic Device (IED)
A0018 Programmable Automation Controller (PAC)
A0003 Programmable Logic Controller (PLC)
A0004 Remote Terminal Unit (RTU)
A0010 Safety Controller

Mitigations

ID Mitigation Description
M0801 Access Management

Authenticate all access to field controllers before authorizing access to, or modification of, a device's state, logic, or programs. Centralized authentication techniques can help manage the large number of field controller accounts needed across the ICS.

M0800 Authorization Enforcement

Systems and devices should restrict access to any data with potential confidentiality concerns, including point and tag information.

M0802 Communication Authenticity

Protocols used for control functions should provide authenticity through MAC functions or digital signatures. If not, utilize bump-in-the-wire devices or VPNs to enforce communication authenticity between devices that are not capable of supporting this (e.g., legacy controllers, RTUs).

M0937 Filter Network Traffic

Perform inline allowlisting of automation protocol commands to prevent devices from sending unauthorized command or reporting messages. Allow/denylist techniques need to be designed with sufficient accuracy to prevent the unintended blocking of valid messages.

M0804 Human User Authentication

All field controllers should require users to authenticate for all remote or local management sessions. The authentication mechanisms should also support Account Use Policies, Password Policies, and User Account Management.

M0807 Network Allowlists

Use host-based allowlists to prevent devices from accepting connections from unauthorized systems. For example, allowlists can be used to ensure devices can only connect with master stations or known management/engineering workstations. [5]

M0930 Network Segmentation

Segment operational assets and their management devices based on their functional role within the process. Enabling more strict isolation to more critical control and operational information within the control environment. [6] [7] [5] [8]

M0813 Software Process and Device Authentication

Devices should authenticate all messages between master and outstation assets.

Detection Strategy

ID Name Analytic ID Analytic Description
DET0788 Detection of Point & Tag Identification AN1920

Real-time monitoring identifies an Industrial Control System (ICS) protocol session that systematically enumerates a device's full tag/object namespace from a source not in the approved control server list, where the enumeration pattern covers the complete address/object space rather than the sparse, fixed tag set legitimate Supervisory Control and Data Acquisition (SCADA) polling queries. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

AN2149

Real-time monitoring identifies an Open Platform Communications (OPC) Unified Architecture (UA) client process on a Linux Industrial Control System (ICS) host calling browse/enumerate operations against the full namespace, from a User Identifier (UID) not associated with recognized monitoring tools. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

AN2177

Real-time monitoring identifies NetFlow showing a source making sequential connections to multiple field device Internet Protocol (IP) addresses, each resulting in large response payloads characteristic of directory listing rather than value reads. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

AN2210

Real-time monitoring identifies an Open Platform Communications (OPC) client process on an Industrial Control System (ICS) Windows host calling BrowseNamespace or GetProperties to enumerate the full tag tree, from a process not associated with a recognized Human-Machine Interface (HMI) or historian tool. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

References