Remote System Discovery: Multicast Discovery

Adversaries may perform multicast discovery requests which is when one system or device sends messages to all systems and devices in a pre-defined group on a network (or subnet) and then waits for a response. If a response is received that means the system or device that responded is live and can communicate over that protocol. Multicast discovery tends to be stealthier than broadcast discovery because every system or device on the network (or subnet) is not being messaged.

One common OT protocol that has a multicast discovery mechanism is the Process Field Network (PROFINET) Discovery and Configuration Protocol (DCP) with its Identify All requests.[1]

ID: T0846.003
Sub-technique of:  T0846
ⓘ
Tactic: Discovery
ⓘ
Platforms: Embedded, Linux, Network Devices, Windows
Version: 1.0
Created: 20 April 2026
Last Modified: 13 October 2026

Procedure Examples

ID Name Description
S1045 INCONTROLLER

INCONTROLLER can perform a UDP multicast scan of UDP port 27127 to identify Schneider PLCs that use that port for the NetManage protocol.[2][3]

Targeted Assets

ID Asset
A0008 Application Server
A0007 Control Server
A0009 Data Gateway
A0006 Data Historian
A0017 Distributed Control System (DCS) Controller
A0016 Firewall
A0002 Human-Machine Interface (HMI)
A0005 Intelligent Electronic Device (IED)
A0012 Jump Host
A0018 Programmable Automation Controller (PAC)
A0003 Programmable Logic Controller (PLC)
A0004 Remote Terminal Unit (RTU)
A0014 Routers
A0010 Safety Controller
A0015 Switch
A0011 Virtual Private Network (VPN) Server
A0001 Workstation

Mitigations

ID Mitigation Description
M0930 Network Segmentation

Ensure proper network segmentation is followed to protect critical servers and devices.

M0814 Static Network Configuration

ICS environments typically have more statically defined devices, therefore minimize the use of both IT discovery protocols (e.g., DHCP, LLDP) and discovery functions in automation protocols.[4][5] Examples of automation protocols with discovery capabilities include OPC UA Device Discovery [6], BACnet[7], and Ethernet/IP.[8]

Detection Strategy

ID Name Analytic ID Analytic Description
DET0909 Detection of Multicast Discovery AN2052

Real-time monitoring identifies Internet Group Management Protocol (IGMP) membership reports for Industrial Control System (ICS) multicast groups from a source not in the approved device inventory. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

AN2163

Real-time monitoring identifies a Linux process joining Industrial Control System (ICS) multicast groups via socket() with IP_ADD_MEMBERSHIP, from a User Identifier (UID) not associated with any authorized ICS protection system monitoring application. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

AN2234

Real-time monitoring identifies a new Internet Group Management Protocol (IGMP) group join or multicast subscription from a source Media Access Control (MAC)/Internet Protocol (IP) not in the approved device inventory, particularly for protection-relay Generic Object Oriented Substation Event (GOOSE) datasets. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

AN2285

Real-time monitoring identifies a Windows process joining Industrial Control System (ICS) multicast groups from a process not associated with an approved ICS protection relay monitoring tool. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.