Adversaries may automate collection of industrial environment information using tools or scripts. This automated collection may leverage native control protocols and tools available in the control systems environment. For example, the OPC protocol may be used to enumerate and gather information. Access to a system or interface with these native protocols may allow collection and enumeration of other attached, communicating servers and devices.
| ID | Name | Description |
|---|---|---|
| S0093 | Backdoor.Oldrea |
Using OPC, a component of Backdoor.Oldrea gathers any details about connected devices and sends them back to the C2 for the attackers to analyze. [1] |
| S0604 | Industroyer |
Industroyer automatically collects protocol object data to learn about control devices in the environment. [2] |
| S1072 | Industroyer2 |
Industroyer2 leverages a hardcoded list of remote-station IP addresses to iteratively initiate communications and collect information across multiple priority IEC-104 priority levels.[3] |
| ID | Asset |
|---|---|
| A0007 | Control Server |
| A0006 | Data Historian |
| A0017 | Distributed Control System (DCS) Controller |
| A0018 | Programmable Automation Controller (PAC) |
| A0003 | Programmable Logic Controller (PLC) |
| ID | Mitigation | Description |
|---|---|---|
| M0807 | Network Allowlists |
Utilize network allowlists to restrict unnecessary connections to network devices (e.g., comm servers, serial to ethernet converters) and services, especially in cases when devices have limits on the number of simultaneous sessions they support. |
| M0930 | Network Segmentation |
Prevent unauthorized systems from accessing control servers or field devices containing industrial information, especially services used for common automation protocols (e.g., DNP3, OPC). |
| ID | Name | Analytic ID | Analytic Description |
|---|---|---|---|
| DET0734 | Detection of Automated Collection | AN1867 |
Real-time network monitoring identifies a source issuing systematic, sequential Industrial Control System (ICS) protocol reads sweeping the full register/address range across multiple field devices within a short time window, from a source not in the approved control server list. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity. |
| AN2128 |
Real-time monitoring identifies a scripting interpreter process iterating through Industrial Control System (ICS) data sources and writing output to a local file or piping to a network socket, by a User Identifier (UID) not associated with documented automation scripts. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity. |
||
| AN2270 |
Real-time monitoring identifies a host process making sequential Industrial Control System (ICS) protocol reads with output piped to a local staging file, from a process not associated with a recognized Human-Machine Interface (HMI) or historian tool. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity. |