Real-time monitoring identifies Industrial Control System (ICS) protocol requests specifically targeting mode/status registers from a source not in the approved control server or engineering workstation list, where the request pattern is narrowly focused on mode/state data rather than broader process value polling. Directly documented in the Triton attack chain's 'Get Control Program Status' request. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.
| Data Component | Name | Channel |
|---|---|---|
| Network Traffic Content (DC0085) | NSM:Content | S7comm SZL Central Processing Unit (CPU)-state read or Common Industrial Protocol (CIP) Identity Object state attribute read from source not in approved Supervisory Control and Data Acquisition (SCADA) servers |
| Field | Description |
|---|---|
| ApprovedSCADAServers | IP allowlist of legitimate engineering and SCADA systems authorized to query device operating mode. |